Rated current: 1600A 1250A
Rated duration of short-circuit: 4S
Rated peak withstand current: 60KA
Weight of movable parts: 1.4KG
Contacts limit erosion: 3MM
Certificate: ISO9000
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Electric Vacuum Interrupter 1600A 1250A For VCB Vacuum Circuit Breaker

Specification

1Rated currentA16001250
2Circuit resistance at lowest rated contact forceμΩ≤20
3Rated short-circuit breaking currentKA31.5
4Breaking operations of rated short circuit breaking currentTimes50
5Rated short-time withstand currentKA31.5
6Rated duration of short-circuitS4
7Rated peak withstand currentKA60
8Rated short-circuit making currentKA60
9Rated breaking current of single capacitor bankA630
10Rated breaking current of back-back capacitor bankA400
11Rated operating sequenceO-0.3s-CO-180s-CO

Mechanical data

1Weight of movable partsKg1.4
2Closing force due to bellow and atmosphereN140±50
3Force required to hold contacts open at full strokeN230±50

Mechanical requirements

1Clearance between open contactsmm11±1
2Average opening speed(average of first 75% of contact gap)m/s1.1±0.2
3Average closing speed(average of last 30% of contact gap)m/s0.6±0.2
4Rated added external contact final force3100±200
Added external contact force at contact touch pointN2200±150
5Contact bouncing duration at closing operationms≤2
6Closing and Opening non-simultaneity of three-phase contactsms≤2
7Maximum Rebound during openingmm≤2

Life

1Storage lifeYears20
2Mechanical enduranceTimes10000
3Contacts limit erosionMm3